CP-72 CHARACTER FORMAT
The ML–Trim uses three different character formats. Enter the number for the required
format, as listed below.
1 = 8 Data Bits, No Parity, One Stop Bit
2 = 7 Data Bits, Even Parity, One Stop Bit
3 = 8 Data Bits, No Parity, Two Stop Bits
CP-73 CONTROL MASK
The Serial Communications can control some of the digital input functions. Enter the
number for the required functions, as listed below.
0 = F–Stop only
1 = F–Stop, Run, R–Stop
2 = F–Stop, Master/Follower, Setpoint Select
3 = All of the Above
MP-58 SERIAL COMMUNICATIONS ERROR
Serial Communications Error identifies errors in the last transmitted message that was
sent to the ML–Trim by the host computer. The mode that displays a number “1”
indicates the error. In the example below, “Invalid Parameter Code” is the error.
Structure Error (Parity,Framing,No ETX, No STX)
Invalid Parameter Code
Invalid Parameter Data or Out of Data Min-Max Range
Control Mask Error
Code