3 - 62
Table 3-50 Entering Drive Enable Logic Control Parameter
CP Parameter Name Parameter Value
CP-10 Alarm 1 Format
CP-11 Alarm 2 Format
CP-74 Drive Enable Logic
Enter "16" to allocate Dig_Out1 as the drive
enable output.
Enter "16" to allocate Dig_Out2 as the drive
enable output.
Enter "0" in CP-74 to deactivate the drive
enable output (output high) when the Ramped
Reference is zero, and activate the drive
enable output (output low) when the Ramped
Reference is not zero.
Enter "1" in CP-74 to deactivate the drive
enable output when both the Ramped
Reference and the feedback are zero, and
activate the drive enable output when the
Ramped Reference is not zero.